Configuration Options
3-32
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Power modules: Maximum configuration per potential group
Table 3-9 Maximum Configuration per Potential Group
Power Modules
Maximum
Current-Carrying
Capacity
Connectable Modules
PM-E 24 VDC Power
Module
10 A The number of modules that can be
connected depends on the total current of
all the modules in this potential group.
This must not exceed 10 A in total. The
total current is decisively affected by the
digital output modules:
2DO 24 VDC/0.5 A Standard
2DO 24 VDC/0.5 A High Feature
Power module PM-E
24–48 VDC/
120–230 VAC
10 A (24 VDC)
8 A (120/230 VAC)
2DO 24 VDC/0.5 A High Feature
4DO 24 VDC/0.5 A Standard
4DO 24 VDC/0.5 A High Feature
2DO 24 VDC/2 A Standard
2DO 24 VDC/2 A High Feature
4DO 24 VDC/2 A Standard
4DO 24 VDC/2 A High Feature
2DO 24–230 VAC/1 A
Number of identifiers: one module per identifier (maximum 63 identifiers)
Use of the ET 200S with DP masters with a diagnostic frame length of 32 bytes:
– IM151-1 STANDARD / IM151-1 FO STANDARD: no
– IM151-1 HIGH FEATURE / IM151-1 BASIC : yes (length of the diagnostic
frame can be parameterized, see Sections 6.6.2 and 8.1)