Commissioning and Diagnostics
6-43
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Analog Output Module Error Types
Table 6-15 Analog Output Module Error Types
Analog output
modules
Error Type Meaning What to Do
2AO U
Standard
2AO U
High
Feature
2AO I
Standard
2AO I
High
Feature
16
D
10000:
Parameter
assignment
error
Module cannot use the
parameter for the channel:
Inserted module does not
match the one configured.
Parameter assignment error.
Correct the configuration
(compare actual and desired
configuration).
Correct the parameter
assignment (parameter
assignment of wire break
diagnosis only with the permitted
measuring ranges).
9
D
01001: Error Internal module error has
occurred (diagnostic
message on channel 0
applies to the whole
module).
Replace the module.
––– 1
D
00001: Short
circuit
Short circuit of the actuator
supply.
Correct the process wiring.
––– 2AO I
Standard
2AO I
High
Feature
6
D
00110: Open
circuit
Line to the actuator
interrupted.
Correct the process wiring.
1SSI
Table 6-16 1SSI
Error Type
Meaning What to Do
1
D
00001: Short circuit Short circuit of the supply to the
absolute position encoder.
Correct the process wiring.
9
D
01001: Error Internal module error occurred.
Load voltage from the power
module is too low.
Replace the module.
Correct the process wiring.
Check the load voltage.