General Technical Specifications
7-8
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
7.3 Mechanical and Climatic Environmental Conditions
Climatic Environmental Conditions
The following climatic environmental conditions apply:
Environmental Conditions Operating Ranges Remarks
Temperature From 0 to 60C For horizontal installation
From 0 to 40C For all other mounting positions
From 0 to 55 C
(see the restrictions below)*
For vertical installation
Temperature variation 10 K/h
Relative humidity From 15 % to maximum 95 % Without condensation
Air pressure From 1080 hPa to 795 hPa Corresponds to an altitude of
-1000 m to 2000 m
Contaminant concentration
SO
2
: < 0.5 ppm;
Rel. humidity < 60 %, no moisture con-
densation
H
2
S: < 0.1 ppm;
Rel. humidity < 60 %, no moisture con-
densation
Test:
10 ppm; 4 days
1 ppm; 4 days
* Restrictions for the operating range of 0 to 55 _C in a vertical position
The operating range of 0 to 55 C in a vertical installation position is only permitted
for the following modules:
IM151-1 STANDARD: 6ES7 151-1AA02-0AB0
PM-E 24 VDC: 6ES7 138-4CA00-0AA0
2DI 24 VDC Standard: 6ES7 131-4BB00-0AA0
2DI 24 VDC High Feature: 6ES7 131-4BB00-0AB0
4DI 24 VDC Standard: 6ES7 131-4BD00-0AA0
4DI 24 VDC High Feature: 6ES7 131-4BD00-0AB0
2DO 24 VDC/0.5 A Standard: 6ES7 132-4BB00-0AA0
2DO 24 VDC/0.5 A High Feature: 6ES7 132-4BB00-0AB0
4DO 24 VDC/0.5 A: 6ES7 132-4BD00-0AA0
2DO 24 VDC/2 A Standard: 6ES7 132-4BB30-0AA0
2DO 24 VDC/2 A High Feature: 6ES7 132-4BB30-0AB0
4DO 24 VDC/2 A Standard: 6ES7 132-4BD30-0AA0
2RO NO 24120 VDC/5 A, 24230 VAC/5 A: 6ES7 132-4HB00-0AB0

Table of Contents