General Technical Specifications
7-11
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Rated Voltage for Operation
The ET 200S distributed I/O system works with the rated voltage and
corresponding tolerances specified in the following table.
ET 200S Modules Rated Voltage Tolerance Range
Everything except 24 VDC 20.4 to 28.8 VDC
1
motor starters
18.5 to 30.2 VDC
2
120 VAC 93 VAC to 132 VAC (47 Hz to
63 Hz)
230 VAC 187 VAC to 264 VAC (47 Hz to
63 Hz)
1
Static value: Created as functional extra-low voltage with safe electrical
isolation to IEC 60364-4-41
2
Dynamic value: Including ripple at three-phase bridge rectification