Terminal Modules
9-12
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Terminal Assignment
The following table shows the terminal assignment of the terminal module:
Table 9-6 Terminal Assignment of the TM-P30S44-A0 and TM-P30C44-A0 Terminal
Module
View
Terminal Designation
3 24 VDC Load voltage of 24 VDC for: inserted
power module and associated potential
group. DO 0 and DO 1 and P1 and P2
voltage buses
A
4
M Ground
1
3
9
4
8
AA
5 AUX 1 Any connection for PE or voltage bus up
to the maximum rated load voltage of the
module
2
3
6
7
1
0
1
1
1
4
1
5
A
6 24 VDC Load voltage of 24 VDC for: inserted
power module and associated potential
group. DO 0 and DO 1 and P1 and P2
voltage buses
1
2
1
6
A
4
A
8
7 M Ground
2
6
A
8
AUX 1 Any connection for PE or voltage bus up
to the maximum rated load voltage of the
module
9 DO 0 P
Connections for fail-safe digital output 0
10 DO 0 M
(switching to P/M potential)
11 DO 2 P
Connections (relay contacts) for fail-safe
switching of the voltage buses P1 and P2.
P1 and P2 can also be used as DO 2 M
12 DO 2 M
P1 and P2 can also be used as DO 2 M
and DO 2 P (for a diagram of the wiring,
see the ET 200S Fail-Safe Modules
manual).
13 DO 1 P
Connections for fail-safe digital output 0
14 DO 1 M
(switching to P/M potential)
15 DO 2 P
Connections (relay contacts) for fail-safe
switching of the voltage buses P1 and P2.
P1 and P2 can also be used as DO 2 M
16 DO 2M
P1 and P2 can also be used as DO 2 M
and DO 2 P (for a diagram of the wiring,
see the ET 200S Fail-Safe Modules
manual).
!
Caution
If high currents occur at DO 2 P and DO 2 M, you must wire terminals 11 and 15
(DO 2 P) and 12 and 16 (DO 2 M) in parallel.
Otherwise, the temperature of the terminals cannot be prevented from rising due
to the current load.