Power Modules
10-10
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Technical Specifications
Dimensions and Weight
Dimensions W H D
(mm)
Weight
15 81 52
34g
Voltage, Currents, Potentials
Rated load voltage 24–56.7 VDC
24–48 VAC/
120–230 VAC
Overvoltage protection Yes
Max. current-carrying
capacity
10 A
For 24–56.7 VDC Up to 30 °C:
max. 10 A
Up to 40 °C:
max. 9 A
Up to 60 °C:
max. 7 A
For 24–48/120/230 VAC Up to 30 °C:
max. 8 A
Up to 40 °C:
max. 7 A
Up to 60 °C:
max. 5 A
Short-circuit protection Yes, IEC 127-2/1,
250 V, 10 A, fast
fuse (5 x 20 mm),
replaceable
1
Isolation
Between rated load
voltage and backplane
bus
Yes
Between the
power modules
Yes
Insulation tested with 4000 VDC
Current consumption
From the backplane bus
Max. 9.5 mA
From load voltage L1/L+
(no load)
Max. 9 mA
Power dissipation of the
module
Max. 5 W
Status, Interrupts, Diagnostics
Diagnostic function Yes
Group error
Load voltage monitoring
Red “SF” LED
Green “PWR” LED
Fuse Green “FSG” LED
Diagnostic information
can be displayed
Yes
1
The fuses on this module are only additional
fuses. External overcurrent protection (suitable
for branch circuits in accordance with the
applicable national regulations for electrical
engineering) is required in the supply lines of the
load circuit.