Digital Electronic Modules
11-29
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 11-8 Terminal Assignment of the 4DI 24–48 VUC High Feature
View RemarksTerminal Assignment
2
3
6
7
1
5
2 conductors 3 conductors
TM-E15S23-01 and 4DI 24–48 VUC High Feature
CH1CH0
DI
2
DI
0
DI
1
DI
3
24/48 VAC/VDC 24/48 VAC/VDC
Channel 0:
Terminals 1 and 3
Channel 1:
Terminals 2 and 3
Channel 2:
Terminals 5 and 7
Channel 3:
Terminals 6 and 7
DI: Input signal
24 VDC sensor supply
2
3
4
6
7
8
1
5
2 conductors 3 conductors
TM-E15S26-A1 and 4DI 24–48 VUC High Feature
CH1CH0
DI
2
DI
0
DI
1
DI
3
24/48 VAC/VDC
24/48 VAC/VDC
24/48 VAC/VDC
24/48 VAC/VDC
8
7
44
3
A
AA
A
AUX1 AUX1
AUX1 AUX1
Channel 0:
Terminals 1 and 3
Channel 1:
Terminals 2 and 4
Channel 2:
Terminals 5 and 7
Channel 3:
Terminals 6 and 8
DI: Input signal
24 VDC sensor supply
AUX: Terminals A4, A3,
A8 DC/AC and A7 can be
used for unused cables
up to 30 VDC.