Analog Electronic Modules
12-24
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Ranges for Resistance-Type Sensors: 150 300
Table 12-31SIMATIC S5 Format: Measuring Ranges 150Ω, 300Ω,
Measuring Range
Units Data Word Range
(Deci-
150 300
(Deci-
mal)
12 11109876543210XEO
> 176.37 > 352.73 2409 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0 1 Overflow
176.37 352.73 2408 0 1 0 0 1 0 1 1 0 1 0 0 0 0 0 0 Overrange
150.07 300.14 2049 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
150 300 2048 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Rated
0.07 0.14 1 0 0 0 0000000001000
range
0 0 0 0 0 0 0000000000000
Negative values 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 Under-
(not physically possible)
360 1 1 1 1 0 1 0 0 1 1 0 0 0 0 0 0
range*
361 1 1 1 1 0 1 0 0 1 0 1 1 1 0 0 1 Underflow*
* If the resistors are connected incorrectly
Measuring Ranges for Resistance-Type Sensors: 6003000
Table 12-32SIMATIC S5 Format: Measuring Ranges 600Ω, 3000Ω,
Measuring Range
Units Data Word Range
(Deci-
600 3000
(Deci-
mal)
12 11109876543210XEO
> 705.47 > 3527.34 2409 0 1 0 0 1 0 1 1 0 1 0 0 1 0 0 1 Overflow
705.47 3527.34 2408 0 1 0 0 1 0 1 1 0 1 0 0 0 0 0 0 Overrange
600.29 3001.46 2049 0 1 0 0 0 0 0 0 0 0 0 0 1 0 0 0
600 3000 2048 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Rated
0.29 1.46 1 0 0 0 0000000001000
range
0 0 0 0 0 0 0000000000000
Negative values 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 Under-
(not physically possible)
360 1 1 1 1 0 1 0 0 1 1 0 0 0 0 0 0
range*
361 1 1 1 1 0 1 0 0 1 0 1 1 1 0 0 1 Underflow*
* If the resistors are connected incorrectly