EasyManua.ls Logo

Siemens ET 200S - Page 420

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-64
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Type of Measurement - Temperature Coefficient - Measuring Range
The following table lists the temperature coefficients and measuring ranges you
can set for each measurement type:
Type of Measurement Temperature Coefficient Measuring Range
Deactivated - -
Four-conductor resistor
Three-conductor resistor
- 150 / 300 / 600 / 3000
Two-conductor resistor - 150 / 300 / 600 / 3000 /
PTC
Three-conductor thermal resistor Pt 0.003850/ Pt 0.003916 /
Pt 0.003902 / Pt 0.003920 /
Pt 0.003851
1
Pt100 climatic range /
Pt100 standard range /
Pt200 climatic range /
Pt200 standard range /Pt200 standard range /
Pt500 climatic range /
Pt500 standard range /
Pt1000 climatic range /
Pt1000 standard range
Ni 0.006180
1
/ Ni 0.006720 Ni100 climatic range /
NI100 standard range /
Ni120 climatic range /
Ni120 standard range /
Ni200 climatic range /
Ni200 standard range /
Ni500 climatic range /
Ni500 standard range /
Ni1000 climatic range /
Ni1000 standard range
Cu 0.00427
1
Cu10 climatic range /
Cu10 standard range

Table of Contents

Related product manuals