Temperature Coefficient
The correction factor for the temperature coefficient ( value) specifies how much
the resistance of a certain material changes when the temperature is raised by
1C.
The temperature coefficient depends on the chemical composition of the material.
Only one value is used in Europe for each type of sensor (default value).
Additional values enable you to make a sensor-specific setting for the temperature
coefficient, therefore ensuring more accuracy.
Parameters for
2AO U Standard, 2AO U High Feature analog electronic module
2AO I Standard, 2AO I High Feature analog electronic module
Table 12-76Parameters for Analog Output Modules U, I
2AO U
Standard,
2AO U High
Feature
2AO I
Standard,
2AO I High
Feature
Value Range Default Applicability
Group diagnosis (parameter
assignment error, internal
error)
Disable
Enable
Disable Module
Diagnostics:
Short-circuit
to M
––– Disable
Enable
Disable Channel
––– Diagnostics:
Wire break
Disable
Enable
Disable Channel
Reaction to
CPU-/Master-STOP
Output de-energized
Substitute a value
Keep last value
Output
de-energized
Module
Type/range
of output
––– Deactivated
1 to 5 V
" 10 V
"10 V Channel
––– Type/range
of output
Deactivated
4 to 20 mA
" 20 mA
4 to 20 mA Channel
Substitute value
1
0 to 65535 (value range must
be inside the rated range)
"10 V/"20 V:
0 V
4 to 20 mA: 4 mA
1 to 5 V: 1 V
Channel
1
If there is no voltage going to the IM but the supply to the analog output modules continues, the
parameterized substitute values are output. Substitute values must be within the nominal range. You can
assign as parameters values from –27648 to +27648 (in the case of parameter assignment by means of
the device database file).