Analog Electronic Modules
12-68
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Smoothing in the case of the 2AI U High Speed, 2AI I 2WIRE High Speed,
2AI I 4WIRE High Speed
0.5
1
0
0.63
100 200 300
Module cycles
400 500 600
None: k=1
Weak: k=64 Medium: k=128 Strong: k=512
Step response
Figure 12-6 Smoothing in the Case of the 2AI U High Speed, 2AI I 2WIRE High Speed,
2AI I 4WIRE High Speed
Interference Frequency Suppression
The 2AI U High Feature and 2AI I 2/4WIRE High Feature analog input modules
support the interference frequency suppression setting (50 Hz or 60 Hz) for the
interface module. These High Feature analog input modules also allow you to
disable interference frequency suppression, thus ignoring the setting made on the
interface module. If you disable interference frequency suppression, the
conversion and cycle times become faster for these modules.