EasyManua.ls Logo

Siemens ET 200S - Page 437

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-81
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Analog Value Generation
Measuring principle Instantaneous value
encoding
Cycle time/Resolution:
Conversion time in ms
(per channel)
0.1
Cycle time in ms (per
module)
1
Resolution (including
overrange)
" 10 V/13 bits +
sign
" 5 V/13 bits + sign
"
2.5 V/13 bits +
sign
1 to 5 V/13 bits
Suppression of Interference, Limits of Error
Common mode
interference (U
cm
)
< 100 V
SS
> 70 dB
Crosstalk between the
inputs
> 50 dB
Operational limit
(entire temperature range
with reference to input
range)
" 3%
Basic error limit (operational
limit at 25 C with reference
to input range)
"0.2%
Temperature error (with re-
ference to the input range)
"0.01%/K
Linearity error (with refe-
rence to the input range)
"0.01%
Repeatability
(in steady state at 25 C
with reference to input
range)
"0.05%
Data for Selecting a Sensor
Input ranges (rated
value)/input resistance
Voltage "10 V/min. 100 k
"5 V/min. 100 k
"2.5 V/min. 100 k
1 5 V/min. 100 k
Maximum input voltage for
voltage input (destruction
limit)
50 V continuous,
100 V for max. 1 ms
(pulse duty factor
1:20)
Connection of the sensors
For measuring voltage Possible
Smoothing of the measured
values
Yes, parameteriza-
ble in 4 steps by
means of digital filte-
ring
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
64 x cycle time
256 x cycle time
512 x cycle time
1
DPV1 only
2
Parameter assignment error
Violation of lower limit value
Violation of upper limit value
Open circuit (only with 1 to 5 V)
Hardware interrupt lost

Table of Contents

Related product manuals