Analog Electronic Modules
12-91
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Terminal Assignment
The following table indicates the terminal assignment of the 2AI I 4WIRE Standard
for the different terminal modules:
Table 12-82Terminal Assignment of the 2AI I 4WIRE Standard
View
Terminal Assignment Remarks
M
1
M
0
2
3
4
6
7
8
15
M
1+
M
0+
mA
M
ana
M
ana
TM-E15S24-01 and 2AI I 4WIRE Standard
24 VDC
24 VDC
4 conductors
CH0
CH1
mA
Channel 0: Terminals 1 to 4
Channel 1: Terminals 5 to 8
M+: Input signal +
M: Input signal “–”
24 VDC: Power supply for
four-wire measuring
transducer
M
ana
: Ground (of power
module)
Four-wire measuring
transducer is supplied by
means of the module.
M
1
M
0
2
3
4
6
7
8
15
M
1+
M
0+
mA
M
ana
M
ana
TM-E15S26-A1 and 2AI I 4WIRE Standard
24 VDC
24 VDC
4 conductors
CH0
CH1
mA
AUX1
A
4
A
3
A
8
A
7
AUX1
AUX1
AUX1
Channel 0: Terminals 1 to A3
Channel 1: Terminals 5 to A7
M+: Input signal +
M: Input signal “–”
24 VDC: Power supply for
four-wire measuring
transducer
M
ana
: Ground (of power
module)
Four-wire measuring
transducer is supplied by
means of the module.