Analog Electronic Modules
12-106
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
12.14 2AI RTD High Feature Analog Electronic Module
(6ES7 134-4NB50-0AB0)
Order Number
6ES7 134-4NB50-0AB0
Features
2 inputs for resistance thermometers or resistance measurement
Input ranges
Resistance thermometers: Pt100; Ni100; Ni120; Pt200; Ni200; Pt500; Ni500;
Pt1000; Ni1000; Cu10;
resolution max. 15 bits + sign
Resistance measurement: 150 300 600 3000 PTC;
resolution max. 15 bits
Automatic compensation of line resistances in the case of a three-conductor
connection
Temperature coefficient can be parameterized for resistance-type sensors
High degree of accuracy
Isolated from the load voltage
Linearization of the sensor characteristic curves
Parameter length 7 bytes
Permitted common-mode voltage 5 VACss
Recording of reference junction temperature (together with the 2AI TC Standard
electronic module)
Compatible with the 2AI RTD Standard (6ES7 134-4JB50-0AB50)
Note
The EM 2AI RTD High Feature can replace a 2AI RTD Standard in an existing
system.
The wiring does not have to be changed. The additional bridges on the terminal
module of the 2AI RTD Standard do not have to be removed.
The configuration (in HWCONFIG or the DDB file) does not have to be
changed. Only the new functions of the 2AI RTD High Feature cannot be
parameterized in this instance.