Analog Electronic Modules
12-113
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Assignment in the Process Input Image (PII) in the case of SIMATIC S7
IB x
76 02
0: measured resistance < response threshold
1: measured resistance > response threshold
1345
0000000
IB x + 1
76 021345
00000000
Assignment in the Process Input Image (PII) in the case of SIMATIC S5
IB x
76 02
0: measured resistance < response threshold
1: measured resistance > response threshold
1345
000000
IB x + 1
76 021345
00000000
0
Notes on programming
Important
Only bit 0/ 3 is relevant for the purposes of evaluation in the process input
image. You can use bit 0/ 3 to monitor the temperature of a motor, for example.
Bit 0/ 3 in the process input image does not have a retentive function. Make
sure at parameter assignment that motor start-up is controlled (by means of an
acknowledgment), for example.
For security reasons, always evaluate the diagnostic inputs of the 2AI RTD
High Feature because measurement is not possible when the EM is removed,
when the power supply to the EM has failed, or in the event of a wire break or
short-circuit of the measuring lines.