Analog Electronic Modules
12-115
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 12-87Terminal Assignment of the 2AI TC Standard
View RemarksTerminal Assignment
2
3
4
6
7
8
1
5
M
ana
M
ana
TM-E15S24-01 and 2AI TC Standard
M
1
M
0
M
1+
M
0+
CH0 CH1
n. c.n. c.
Channel 0: Terminals 1 to 4
Channel 1: Terminals 5 to 8
M+: Measuring line (positive)
M: Measuring line (negative)
M
ana
: Ground of the module
Terminals 4 and 8 can be
used for unneeded wires of
up to 30 VDC.
2
37
1
5
M
ana
M
ana
TM-E15S23-01 and 2AI TC Standard
M
1
M
0
M
1+
M
0+
CH0 CH1
Channel 0: Terminals 1 to 3
Channel 1: Terminals 5 to 7
M+: Measuring line (positive)
M: Measuring line (negative)
M
ana
: Ground of the module
2
3
4
6
7
8
1
5
M
ana
M
ana
TM-E15S26-A1 and 2AI TC Standard
M
1
M
0
M
1+
M
0+
CH0 CH1
AUX1
A
4
A
3
A
8
A
7
AUX1
AUX1
AUX1
n. c.n. c.
Channel 0: Terminals 1 to A3
Channel 1: Terminals 5 to A7
M+: Measuring line (positive)
M: Measuring line (negative)
M
ana
: Ground of the module
Terminals 4 and 8 can be
used for unneeded wires of
up to 30 VDC.