Analog Electronic Modules
12-117
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Analog Value Generation
Measuring principle Integrative
Integration time/conversion
time/resolution per channel:
Integration time
parameterizable
Yes
Interference frequency
suppression in Hz
60 50
Integration time in
milliseconds
16.7 20
Basic conversion time
including Integration
time in milliseconds
55 65
Additional conversion
time for wire break
check diagnosis in ms
20 20
Cycle time in ms Number of active
channels per
module
conversion time
Resolution (including
overrange)
15 bits plus sign
Suppression of Interference, Limits of Error
Interference voltage sup-
pression for f = n x
(f1"1%), (f1 = interference
frequency)
Common-mode
interference (U
pp
)
Series-mode
interference
(peak interference
value < rated value of
input range)
Min. 90 dB
Min. 70 dB
Crosstalk between the in-
puts
Min. –50 dB
Operational limit (in the en-
tire temperature range, with
reference to the input
range)
1
"0.6%
Basic error limit (operational
limit at 25C with reference
to input range)
1
"0.4%
Temperature error (with re-
ference to the input range)
"0.005%/K
Linearity error (with refe-
rence to the input range)
"0.01%
Repeatability
(in steady state at 25C
with reference to input
range)
"0.05%
Data for Selecting a Sensor
Input range (rated
value)/input resistance
Voltage "80 mV/min. 1 MΩ
Thermocouple Type E, N, J, K, L, S,
R, B, T/min. 1 MΩ
Permitted input voltage
(destruction limit)
"10 V, continuous
Connection of the sensors
For measuring voltage Possible
Characteristic curve lineari-
zation
Yes, parameteriza-
ble for type E, N, J,
K, L, S, R, B, T to
IEC 584
Temperature compensation
Internal temperature
compensation
Not possible
External temperature
compensation by
looping a compensating
box into the measuring
circuit
Possible, one
external
compensating box
per
channel
External compensation
by means of
temperature value
obtained at an analog
module of the same
ET 200S station
Yes
Smoothing of the measured
values
Yes, parameteriza-
ble in 4 steps by
means of digital filte-
ring
Step
None
Weak
Medium
Strong
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
1
For type N: as of –150 C,
type B: as of 200 C,
type T: as of –230 C