EasyManua.ls Logo

Siemens ET 200S - Page 482

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-126
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Analog Value Generation
Resolution (including over-
range)
10 V/13 bits + sign
1 to 5 V/12 bits
Cycle Time Max. 1.5 ms
Settling time
For resistive load 0.1 ms
For capacitive load 0.5 ms
For inductive load 0.5 ms
Substitute value paramete-
rizable
Yes
Suppression of Interference, Limits of Error
Crosstalk between the out-
puts
min. 40dB
Operational limit (in the en-
tire temperature range, with
reference to the output
range)
"0.4%
Basic error limit (operational
limit at 25 C with reference
to output range)
"0.2%
Temperature error (with re-
ference to the output range)
"0.01%/K
Linearity error (with refe-
rence to the output range)
"0.02%
Repeatability
(in steady state at 25 C
with reference to output
range)
"0.05%
Output ripple (with refe-
rence to output range,
bandwidth 0 to 50 kHz)
"0.02%
Data for Selecting an Actuator
Output range (rated value) "10 V
1 to 5 V
Load resistance Min. 1.0 k
For capacitive load Max. 1 µF
Short-circuit protection Yes
Short-circuit current Approx. 25 mA
Destruction limit against
voltages/currents applied
from outside
Voltage at the outputs to
M
ANA
Max. 15 V
continuous; 75 V for
max. 1 s (pulse duty
factor 1:20)
Current Max. DC 50 mA
Connection of actuators
Two-conductor
connection
Possible, without
compensation of the
line resistances
Four-conductor
connection
Yes

Table of Contents

Related product manuals