4 IQ-SENSE
13-16
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
13.3 Terminal Assignment
The following table indicates the terminal assignment of the 4 1Q-SENSE for the
different terminal modules:
Table 13-5 Terminal Assignment of the 4 IQ-SENSE
View
Terminal Assignment Remarks
2
3
4
6
7
8
1
5
TM-E15S24-01 and 4 IQ-SENSE
CH1CH0
M
0+
CH2 CH3
M
2+
M
0
M
2
M
1+
M
3+
M
1
M
3
Sensor
Sensor
Channel 0:
Terminals 1 and 3
Channel 1:
Terminals 5 and 7
Channel 2:
Terminals 2 and 4
Channel 3:
Terminals 6 and 8
M
+
: Input signal+
M
: Input signal “–”
2
3
4
6
7
8
1
5
TM-E15S26-A1 and 4 IQ-SENSE
CH1
CH0
CH2
CH3
A
4
A
3
A
8
A
7
AUX1
AUX1
M
0+
M
2+
M
0
M
2
M
1+
M
3+
M
1
M
3
AUX1
AUX1
Sensor
Sensor
Channel 0:
Terminals 1 and 3
Channel 1:
Terminals 5 and 7
Channel 2:
Terminals 2 and 4
Channel 3:
Terminals 6 and 8
M
+
: Input signal+
M
: Input signal “–”
Note
The connections to the sensors are protected against polarity reversal.
The minimum conductor cross-section for the sensors is 0.25 mm
2
The connecting cable for the sensors is described in Appendix A.