Maintenance / Repair
8
Faults
103
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
Fault/problem
Possible cause
Remedy
Topmost or
bottommost LED
flashes
LED lights up
Additional deviation in the airflow outside
the set limit parameters.
Check the pipe system for damage, e.g.,
cracks, holes, loose connections between
the pipes and fittings.
Blow out the pipe system.
Normalize the aspirating smoke detector.
If connected to FDnet/C-NET:
Following an alarm, flashing LED alarm indicators
on the aspirating smoke detector can only be reset via the fire control panel/fire
terminal.
See also
Fault analysis [➙ 104]
LED and buzzer test [➙ 89]