Structure and function
3
Function
35
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
3.5.1.1 Danger levels
The aspirating smoke detector can transmit the following danger levels to the fire
control panel:
Symbol
Danger level _ 1
1
2 3 3
Designation _ Inspect Prealarm Fire 1 Fire 2
Configuration in the
fire detection
installation
_ Sensor 1 Sensor 2
Meaning No danger Possible danger
Warning Alarm Alarm and extinguishing
Alarm level: Fire 2
Comment Normal Check situation Possible
danger
Fire The highest danger level 3 has been
reached and the conditions for
activating extinguishing are satisfied.
1
If danger level 1 is frequently transmitted, check whether another sensitivity
setting is more suitable.
The evaluation of the danger level and the decisions to be taken (e.g. activation of
remote transmission) are configured in the fire detection system.
3.5.1.2 Interface to service devices
A port with the MC link (maintenance and commissioning link) is installed on
communication transponder FDCC221S.
Using this interface, it is possible to read data from the device with the 'FDUD292
detector exchanger and tester' or the 'FDUD293 intelligent detector tester'.
You will find more information in documents 007227 and 009718.
See also
Applicable documents [➙ 9]

Table of Contents

Other manuals for Siemens FDA241 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA241 Series and is the answer not in the manual?

Siemens FDA241 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA241 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals