EasyManuals Logo

Siemens FDA241 Series Technical Manual

Siemens FDA241 Series
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #84 background imageLoading...
Page #84 background image
7
Commissioning
Functional testing of the system
84
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
7.3.2 Functional testing of the system with the standalone option
NOTICE
Accidental triggering of an alarm
Using smoke or aerosols for testing purposes may trigger an alarm
unintentionally.
Make sure no alarm is sent to the fire brigade during the test.
Testing without alarm transmission/triggering of an alarm
Communication transponder FDCC221S is not installed.
A smoke stick/aerosol spray is available.
A connected fire detection installation must be configured as appropriate for the
test.
1. Open the housing cover. [➙ 46]
The front indicator indicates a fault
.
The relay outputs are active and the 'Smoke 4…20 mA' analog output has
been switched to fault (0.5 mA).
2. If the relay outputs are to be deactivated for this test, press the
button. Observe the information on page [➙ 46].
3. Move the smoke/aerosol toward an aspirating hole in the pipe system.
Select an aspirating hole that is a long distance away if you want to test the
response time as well.
4. Check whether the smoke indicator [➙ 24] rises fully and whether the internal
indicator [➙ 28] displays 'Alarm'.
5. Wait until the smoke indicator has dropped to no more than 5 LEDs.
6. Close the housing cover.
The fault indicator goes out.
That is the end of the test.

Table of Contents

Other manuals for Siemens FDA241 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA241 Series and is the answer not in the manual?

Siemens FDA241 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA241 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals