Technical data for FDA241, FDA221
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
Pipe outer diameter 25 mm
Inner diameter of pipe 21 mm
Maximum piping lengths for FDA241:
Single line FDA241: 60 m
Branched lines FDA241: 2 x 60 m
Maximum piping lengths for FDA221:
Single line 30 m
Branched lines 2 x 25 m
The maximum permissible surface depends on the locally valid regulations!
Maximum surface:
FDA241 800 m²
FDA221 500 m²
Compatibility (FDCC221S installed)
Compatible with fire control panels FC20xx/FC72x
Operating temperature -20…+60 °C
Storage temperature -30…+70 °C
Air humidity 5…95 % rel.,
no moisture
condensation
Protection category (IEC 60529):
FDA241 IP30
FDA221 IP30
Weight approx. 1.5 kg
Housing material ABS/PC
Housing color ∽RAL 9010 pure white
European standards EN 54-20 A, B, C
EN 54-17 with
FDCC221S installed