Commissioning
7
Operation on addressed detector line
81
Building Technologies A6V10334410_h_en_--
Fire Safety 2015-09-29
Field
Action
Smoke delay time Set the alarm delay for smoke detection.
You can choose from the following:
1
Device default
0 sec (EN54-20)
15 sec
60 s
120 sec
300 sec
For firmware versions ≤ 3.6:
To prevent false alarms, an alarm delay of '60 s' is set by default.
For conformity to standards, the alarm delay can be reduced to '0
sec (EN54-20)'.
For firmware versions ≥ 3.10:
To prevent false alarms, an alarm delay of '0 s' is set by default.
Device test mode Switch on / isolate test mode.
You can choose from the following:
Normal operation
Test mode enabled
Following an alarm, flashing LED alarm indicators
on the aspirating smoke detector can only be reset via the fire control panel/fire
terminal.
You will find more information in the following documents:
For fire control panels FC20xx: Document 009078
For fire control panels FC72x: Document A6V10210424
See also
Applicable documents [➙ 9]

Table of Contents

Other manuals for Siemens FDA241 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA241 Series and is the answer not in the manual?

Siemens FDA241 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA241 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals