Preparations for use
4.1 Transport and storage
WOGeneric TEAAC / 2008
Siemens AG Operating Instructions 1.03 1RQ671...-Z 19
In the bearing end shields on the drive end and non-drive end, water drainage holes are
situated lower down and opposite the regreasing devices. They are sealed with small plastic
plugs or screws. Depending on the type of installation, the water drainage holes are located
at the bottom.
1. Remove the screws or the plastic plugs regularly to allow the condensate to drain away.
2. Replace them when you have finished.
NOTICE
Degree of protection
The degree of protection of motors with IP54 or higher is nominally reduced to IP44 by
removal of the plastic plug or screw.
[ID 1079.03]