Siemens AG Operating Instructions 1.03 1RQ671...-Z 25
Connection
6
6.1 Electrical connection
6.1.1 Grounding the motor
The cross-section of the machine grounding conductor must comply with the installation
regulations, e.g., in accordance with IEC/EN 60204-1, for phase conductor cross-sections
greater than 35 mm
2
, with a minimum of 50% of the-cross section of the phase conductor.
There is a hexagon bolt with flat and spring washer on the stator frame at the designated
connecting point for the grounding conductor. This is suitable for connecting multi-core
conductors with cable lugs or straps with appropriate conductor ends.
Connecting the grounding conductor
When making connections, ensure the following:
The connecting surface is bare and is protected against corrosion using a suitable
substance, e.g., acid-free Vaseline
The spring lock and spacer washer are located under the bolt head
The maximum permissible clamping thickness of 10 mm for the cable lug or strap is not
exceeded
The minimum required screw-in depth and the tightening torque for the clamping bolt as
given in the table below are observed
The screw-in depth and tightening torque differ depending on whether cable lugs or
ground terminals are used:
Table 6-1 Tightening torques of bolts (cable lug)
Bolt Screw-in depth Tightening torque
M12 x 25 > 16 mm 38 Nm
M16 x 35 > 20 mm 92 Nm
Table 6-2 Tightening torques of bolts (ground terminals)
Bolt Screw-in depth Tightening torque
M6 > 9 mm 8 Nm
M8 > 12 mm 20 Nm
M10 > 15 mm 40 Nm