Functions of the IM 151-7 CPU
8-2
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
8.1 Data for the PROFIBUS-DP
Device master file
A DDB file contains all the slave-specific properties. The structure of the DDB file
is defined in IEC 61784-1:2002 Ed1 CP 3/1.
You only need the DDB file if:
You are using the ET 200S with a DP master from the SIMATIC S5 range
(configuration with COM PROFIBUS)
You are using the ET 200S with a non-SIMATIC DP master (configuration with a
non-Siemens tool).
You can download the DDB file from the Internet. You will find all the DDB files
under ”Downloads” on the SIMATIC Customer Support web site:
http://www.ad.siemens.de/csi/gsd
Important features
If you do not have the DDB file to hand, the following table lists the most important
features of the IM 151-7 CPU.
Table 8-1 Attributes from the device database (DDB) file
Feature
DP code word to
IEC 61784-1:2002 Ed1 CP 3/1
IM 151-7 CPU
Manufacturer ID Ident_Number 80E2
H
Supports FMS FMS_supp No
Supports 9.6 kbaud 9.6_supp Yes
Supports 19.2 kbaud 19.2_supp Yes
Supports 45.45 kbaud 45.45_supp Yes
Supports 93.75 kbaud 93.75_supp Yes
Supports 187.5 kbaud 187.5_supp Yes
Supports 500 kbaud 500_supp Yes
Supports 1.5 Mbaud 1.5M_supp Yes
Supports 3 Mbaud 3M_supp Yes
Supports 6 Mbaud 6M_supp Yes
Supports 12 Mbaud 12M_supp Yes
Supports the FREEZE control command Freeze_Mode_supp Yes
Supports the SYNC control command Sync_Mode_supp Yes
Supports automatic transmission rate detection Auto_Baud_supp Yes
PROFIBUS address modifiable by software Set_Slave_Add_supp No
Length of user-specific parameter assignment data User_Prm_Data_Len 3 bytes
User-specific parameter assignment data User_Prm_Data Yes