EasyManua.ls Logo

Siemens IM 151-7 - PROFIBUS Address

Siemens IM 151-7
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ET 200S in the PROFIBUS Network
4-8
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
4.3 PROFIBUS address
Features
Use the PROFIBUS address to specify the address at which the IM 151-7 CPU is
contacted on the PROFIBUS-DP.
Prerequisites
The permitted PROFIBUS-DP addresses are 1 to 125.
Each address can be allocated only once on the PROFIBUS-DP.
Startup without DP configuration on the Micro Memory Card (MMC) (initial
startup)
Following POWER ON, the coexistent interface on the IM 151-7 CPU powers up
as an MPI interface with the address 2, HSA 31 and 187.5 kBaud. The I slave
functionality of the IM 151-7 CPU is not yet available. All PD functions listed in
Section 4.4 are possible with the interface.
Several ET 200S units with IM 151-7 CPUs as I slaves on one PROFIBUS network
must be commissioned step by step. After each individual IM 151-7 CPU has been
switched on, STEP 7 must be used to transfer a configuration with DP address to
the IM 151-7 CPU.
Note
The bus parameters are retentive, i.e.bus parameters that have been configured
(e.g. address, transmission rate) are retained
with POWER OFF
if there is no longer a configuration on the IM 151-7 CPU (e.g. after SDBs have
been deleted or following POWER ON without MMC)
Startup with DP configuration on the Micro Memory Card (MMC)
As soon as a DP configuration has been downloaded to the IM 151-7 CPU, the
data stored on the MMC is used on startup.
Following POWER ON, the IM 151-7 CPU as the I slave powers up with the
configured address and waits for parameter assignment by the DP master.
As active PROFIBUS node, the IM 151-7 CPU adopts the configured transmission
rate.
As passive PROFIBUS node, the IM 151-7 CPU searches for the transmission
rate.

Table of Contents

Related product manuals