A5E00067781 01
84
4.4.3 On/Off Delay
Brief description
In the case of the on/off delay, the output is switched
through after a programmable time and reset after a para-
meterizable time period has elapsed.
Symbol in
LOGO!
Connection Description
Input Trg A rising edge (change from
0 to 1) at the input Trg (Trig-
ger) starts the time T
H
for
the on delay.
A falling edge (change from
1 to 0) starts the time T
L
for
the off delay.
Parameter Par T
H
is the time after which
the output is switched on
(output signal is switched
from 0 to 1).
T
L
is the time after which the
output is switched off (out-
put signal is switched from 1
to 0).
Output Q Q switches on after the
parameterized time T
H
has
elapsed if Trg is still set, and
switches off after the time T
L
has elapsed if Trg has not
been set again in the in-
terim.
Parameters T
H
and T
L
Note the default values for the parameters T
H
and T
L
in
Section 4.3.2.
LOGO! Functions

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LOGO! 230RCL and is the answer not in the manual?

Siemens LOGO! 230RCL Specifications

General IconGeneral
Power Supply230V AC
Input Voltage230V AC
Digital Inputs8
Analog Inputs2
Programming SoftwareLOGO! Soft Comfort
Protection classIP20
Mounting typeDIN rail
Digital Outputs4
Operating Temperature0°C to +55°C
Storage Temperature-25°C to 70°C