Installation
5.1 Line-side connection
LOGO!Power
24 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
Note
For operation on a direct voltage network (DC), the plus pole (+) must be connected to L1
and the
minus pole (–) to N.
Recommended line-side protection
6EP1311-1SH03 (5 V / 3 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1311-1SH13 (5 V / 6.3 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1321-1SH03 (12 V / 1.9 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1322-1SH03 (12 V / 4.5 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1351-1SH03 (15 V / 1.9 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1352-1SH03 (15 V / 4 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1331-1SH03 (24 V / 1.3 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1332-1SH43 (24 V / 2.5 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
6EP1332-1SH52 (24 V / 4 A)
Miniature circuit-breaker (IEC 898): Characteristic B from 16 A or characteristic C from 10 A
Other country-specific regulations may have to be observed when installing the device.