EasyManua.ls Logo

Siemens LOGO!Power Series - Technical data; Input specifications

Siemens LOGO!Power Series
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LOGO!Power
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
27
Technical data
6
Note
For an AC input voltage, the technical data is applicable for rated input voltage, rated load
and +25° C ambient temperature (if nothing else is specified).
6.1
Input
6EP1311-1SH03
(5 V / 3 A)
6EP1311-1SH13
(5 V / 6.3 A)
6EP1321-1SH03
(12 V / 1.9 A)
6EP1322-1SH03
(12 V / 4.5 A)
6EP1351-1SH03
(15 V / 1.9 A)
Input
1-phase AC or DC
Rated voltage
U
e rated / for AC
100...240 V
Voltage range / for AC
85...264 V
Input voltage / for DC
110…300 V
Wide-range input
Yes
Overvoltage
resistance
2.3 x Ue rated, 1.3 ms
Mains buffering at
Ia rated, min.
40 ms 40 ms 40 ms 40 ms 40 ms
Mains buffering
at Ue = 187 V
Rated line frequency
50/60 Hz
Line frequency range
47...63 Hz
Input current / at rated
value of input voltage
120 V
0.36 A 0.71 A 0.53 A 1.13 A 0.63 A
Input current / at rated
value of input voltage
230 V
0.22 A 0.37 A 0.3 A 0.61 A 0.33 A
Switch-on current
limitation (+ 25° C),
max.
26 A 50 A 25 A 55 A 25 A
I²t, max.
0.8 A²·s
3 A²·s
0.8 A²·s
3 A²·s
0.8 A²·s
Built-in line-side fuse
Internal
Protection in the line
feeder cable (IEC 898)
Recommended miniature circuit-breaker: Characteristic B from 16 A or characteristic C from 10 A