Safety, approvals, EMC
7.4 EMC
LOGO!Power
44 Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
6EP1311-1SH03 (5 V / 3 A)
6EP1311-1SH13 (5 V / 6.3 A)
6EP1321-1SH03 (12 V / 1.9 A)
6EP1322-1SH03 (12 V / 4.5 A)
6EP1351-1SH03 (15 V / 1.9 A)
6EP1352-1SH03 (15 V / 4 A)
6EP1331-1SH03 (24 V / 1.3 A)
6EP1332-1SH43 (24 V / 2.5 A)
6EP1332-1SH52 (24 V / 4 A)
Generic standards
Immunity for industrial environments
Emission for residential areas
Electromagnetic fields EN 61000-4-3 80…1000 MHz 10 V/m
1000…2000 MHz 3 V/m
80...1000 MHz 10 V/m
1000...2000 MHz 3 V/m
High-speed transient disturbance
variables (burst)
EN 61000-4-4 4 kV on line connections
4 kV on line connections
Power surges EN 61000-4-5 2 kV symmetrical on line
connections
4 kV asymmetrical on line
connections
500 V symmetrical/asymmetrical
2 kV symmetrical on line
connections
4 kV asymmetrical on line
connections
500 V symmetrical/asymmetrical
Voltage dips EN 61000-4-11 100% for 20 ms
60% for 200 ms
100% for 20 ms
60% for 200 ms
Line harmonics limitation