Technical data
6.2 Output
LOGO!Power
Operating Instructions, 06.2014, C98130-A7560-A999-3-7629
29
6EP1311-1SH03
(5 V / 3 A)
6EP1311-1SH13
(5 V / 6.3 A)
6EP1321-1SH03
(12 V / 1.9 A)
6EP1322-1SH03
(12 V / 4.5 A)
6EP1351-1SH03
(15 V / 1.9 A)
Regulated, isolated DC voltage
Rated voltage value
5 V 5 V 12 V 12 V 15 V
Total tolerance, static ±
Static line regulation,
0.2% 0.1% 0.1% 0.1% 0.1%
Static load regulation,
1.5% 2% 1.5% 1.5% 1.5%
Residual ripple peak-
100 mV 100 mV 200 mV 200 mV 200 mV
Residual ripple peak-
10 mV 15 mV 10 mV 10 mV 10 mV
Spikes peak-peak,
max. (bandwidth,
100 mV 100 mV 300 mV 300 mV 300 mV
Spikes peak-peak, typ.
(bandwidth, approx.
20 mV 70 mV 20 mV 70 mV 30 mV
Product function /
output voltage can be
Yes
Green LED for output voltage OK
Response when
No overshoot of Ua (soft start)
Current range
• Remark
0…3 A
3 A to +55° C,
0…6.3 A
6.3 A to +55° C,
0…1.9 A
1.9 A to +55° C,
0…4.5 A
4.5 A to +55° C,
0…1.9 A
1.9 A to +55° C,
Output active power /
15 W 30 W 23 W 50 W 23 W
Can be connected in
parallel to increase the
power rating
Yes
Number of devices
that can be connected
in parallel to increase
2
Output characteristic See Figure 6-3 Output characteristic (Page 31)