Operating the removable voltage transformers
139-2021.9 / 07 NXAIR M 123
Selection table for protection fuse-links:
Rated voltage
U
r
[kV]
Rated current
I
r
[A]
Reference
dimension
“e” [mm]
Order details:
24
6.3
292
3018013.6,3
Manufacturer information: www.siba-fuses.com
Removable voltage transformer rating plate
Further technical data is shown on the rating plate of each removable voltage transformer.
Fig. 205: Rating plate on removable voltage transformer
Preconditions
Removable voltage transformers taken out of the panel
Set of proper protection fuse-links available
Procedure
Move the service truck with the removable voltage transformers away from the panel. The
protection fuse-links are accessible.
Fig. 206: Protection fuse-links are accessible