Product data
Technical data
5
26 | 34 A6V11571319_en--_b
PCA2005-A1
Ambient conditions
Operating temperature -10…+55 °C
Storage temperature -20…+70 °C
Operation in humid environments
(without moisture condensation)
10...90 % rel.
Storage in humid environments
(without moisture condensation)
5...90 % rel.
Dimensions and weights
W x H x D mm 70 x 116 x 25
W x H x D mm (housing) 85 x 135 x 37
Weight 65 g
Weight (with housing) 123 g
Standards EN 54-17 with housing PCA2013-A1
1
Calculation of the maximum audio payload:
The maximum audio payload per amplifier channel depends on how many loop
isolators (100 V) are connected.
'Audio payload' [W] = 'power of the amplifier channel' – ('number of loop isolators'
* 0.5 W)
2
Twisted cable types are not permitted
Spelsberg i 16-L loop isolator Box
PCA2013-A1
Rated insulation voltage AC 400 V
Conductor cross-section Max. 2.5 mm
2
Ambient conditions
Operating temperature -25…+40 °C
Max. operating temperature (24 hours) 35 °C
Max. air humidity at 25 °C (short-term) 95 % rel.
Max. air humidity at 40 °C 50 % rel.
Dimensions and weights
W x H x D mm 130 x 85 x 37
Weight 58 g
Material
Box Polyethylene
Cover Polypropylene
Protection category and color
Protection category (IEC 60529) IP55
Color Gray