Perfect Harmony GENIII/e User’s Manual Hardware Components
A1A19000405A: Version 1.3 2-15
ss
ss
2
Table 2-11: 6,600 VAC GENIII/e Cell Specifications: 18 Cells Total, 6 (690 VAC) Cells in Series
The basic electrical diagrams for all Perfect Harmony systems are similar. Depending on the operating voltages,
different numbers of output cells are operated in series to develop the required output operating voltage (refer to the
previous tables).
Hp
1
1. Motor nameplate Hp may not exceed the drive rated Hp.
Amps In
2
2. Drive rated input current (in Amps) is the transformer rated current.
Amps Out
3
3. Drive rated output current (in Amps) is the maximum cell current.
Losses
4
4. Losses are given in BTU/hr and are based on a loss of 3 kW per 100 Hp.
Ventilation
5
5. Minimum ventilation requirements are given in CFM (lps in parentheses).
Length
6
6. Represents lineup minimum length in inches (centimeters in parentheses), subject to change.
Weight
7
7. Represents estimated minimum weight of lineup in pounds (kg in parentheses), subject to change.
Size
8
8. Cell sizes for each Hp are based on motors with 95% efficiency and 85% power factor.
3500 264 315 266,000 28,000 248 21,900 315H
4000 301 315 304,000 28,000 272 23,800 315H
5000 377 375 380,000 28,000 272 27,700 375H
6000 452 500 450,000 28,000 272 31,600 500H
7000 527 660 532,000 28,000 272 35,500 660H
8000 603 660 608,000 28,000 272 39,400 660H