Perfect Harmony GENIII/e User’s Manual The Keypad and Display Interface
A1A19000405A: Version 1.3 3-23
3
Table 3-7: Motor Parameter Menu (1000)
Parameter ID Units Default Min Max Description
Motor frequency 1020 Hz 60 15 330
Enter the rated or base frequency of
the motor from the nameplate.
Full load speed 1030 RPM 1780 1 19800
Enter the full load speed of the motor
from the nameplate.
Motor voltage 1040 V 4160 380 13800
Enter the rated voltage for the motor
from the nameplate.
Full load current 1050 A 125.0 12.0 1500.0
Enter the rated nameplate full load
current of the motor.
No load current 1060 % 25.0 0.0 100.0
Enter the no load current of the motor
if it is provided, or use the Auto-tune
function.
Motor kW rating 1010 kW 746.0 120.0 20000.0
Enter the motor kW (0.746 * Hp)
from the nameplate.
Leakage inductance 1070 % 16.0 0.0 30.0
Enter the leakage inductance of the
motor if it is provided, or use the
Auto-tune function.
Stator resistance 1080 % 0.10 0.00 25.00
Enter the stator resistance of the
motor if it is provided. To convert
from ohms to %, use the formula:
[%Rs = 100 * √3 * Rs (in ohms) *
Motor Current/Motor Voltage], or use
the Auto-Tune function.
Inertia 1090
Kgm
2
30.0 0.0 100000.0
Enter the rotor inertia of the motor if
known (1Kgm
2
= 23.24 lbft
2
), or use
the Auto-Tune function.