Perfect Harmony GENIII/e User’s Manual The Keypad and Display Interface
A1A19000405A: Version 1.3 3-59
3
Table 3-55: Drive Protect Menu (7) Parameters
Parameter ID Units Default Min Max Description
Input Protection 7000 Submenu
Input protection parameters. See
Table
3-56.
Drive IOC Setpoint 7110 % 150.0 50.0 200.0
Drive instantaneous overcurrent
setpoint (as a percentage of drive
output rating).
Cell Overload Level 7112 % 100.0 100.0 150.0
Cell current overload (as a
percentage of drive output
rating) allowed for 1 minute out
of every 10 minutes.
Auto Reset Enable 7120 No
Enables the reset of the Drive
after a fault.
Auto Reset Time 7130 sec 1 0 120
Adjusts the time between the
fault and its automatic reset.
Auto Reset Attempts 7140 4 1 10
The number of attempts a drive
will be reset before a permanent
shutdown.
Auto Reset Memory Time 7150 sec 10 1 1000
The amount of time between
faults that will clear the attempts
counter.
Fault Reset 7160 Function
Issues a Drive fault reset when
selected.