Address Assignment and Installation   
3.1 Address assignments in the F-CPU 
  ET 200S Distributed I/O System - Fail-Safe Modules 
28  Installation and Operating Manual, 08/2008, A5E00103686-07 
Occupied Bits in F-CPU per F-Module: 
x + 0  Channel 
7 
Channel 
6 
Channel 
5 
Channel 
4 
Channel 
3 
Channel 
2 
Channel 
1 
Channel 
0 
4 F-DI/3 F-DO DC24V PROFIsafe: 
x + 0 (inputs)  —  —  —  —  Channel 
3 
Channel 
2 
Channel 
1 
Channel 
0 
x + 0 (outputs)  —  —  —  —  —  Channel 
2 
Channel 
1 
Channel 
0 
4 F-DO DC24V/2A PROFIsafe: 
x + 0  —  —  —  —  Channel 
3 
Channel 
2 
Channel 
1 
Channel 
0 
1 F-RO DC24V/AC24..230V/5A: 
x + 0  —  —  —  —  —  —  0  Channel 
0 
(Readba
ck 
channel)
x = Module start address 
 
 
WARNING 
 
You may only access the addresses occupied by useful data. The other address ranges 
occupied by the F-modules are assigned for functions including safety-related 
communication between the F-modules and F-CPU in accordance with PROFIsafe. 
With the 1oo2 evaluation of sensors, only the less significant channel of the channels that 
are grouped as a result of the 1oo2 sensor evaluation can be accessed in the safety 
program. 
 
Additional Information 
Detailed information about fail-safe I/O access can be found in the 
S7 Distributed Safety, 
Configuring and Programming
 manual or the 
S7 F/FH Systems, Configuring and 
Programming
 manual.