Fail-Safe Modules   
7.4 PM-D F DC24V PROFIsafe Power Module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
96  Installation and Operating Manual, 08/2008, A5E00103686-07 
7.4  PM-D F DC24V PROFIsafe Power Module 
7.4.1  Properties of the PM-D F DC24V PROFIsafe Power Module 
Order Number 
3RK1903-3BA02 
Properties 
The PM-D F DC24V PROFIsafe power module disposes of the following properties: 
●  6 shutdown groups, SG 1 through SG 6 
●  Output current of SG 1 through SG 6, each 3 A (total current 5 A) 
●  Rated load voltage 24 VDC per shutdown group 
●  Suitable for supplying: 
–  Fail-safe motor starters F-DS1e-x, F-RS1e-x 
–  Fail-safe frequency converters F-FU 
–  Fail-safe connection multipliers F-CM 
–  Fail-safe power/expansion modules PM-D F X1 
–  Brake control expansion modules xB1, xB2, xB3 and xB4 
●  Group fault display (SF; red LED) 
●  Status display per shutdown group (SG 1 through SG 6; green LED) 
●  Status display for load current power supply (PWR; green LED) 
●  Status display for electronic power supply (U1; green LED) 
●  achievable safety class SIL3/Category 4/PLe 
Switching the Voltage Buses SG 1 through SG 6 and U 1 
The power module can shut down voltage buses SG 1 through SG 6 over 6 digital outputs 
complying with safety class SIL2/Category 3/PLd or SIL3/Category 4/PLe. The outputs are 
implemented with two P switches. There is a main switch for all 6 shutdown groups and 6 
individual switches connected in series per shutdown group. 
The voltage bus U 1 (electronics power supply for the motor starters) is supplied with 
24 VDC. When overvoltage or undervoltage occurs,  U 1 is switched off by two P switches 
and the downstream motor starters are passivated. In the event of a safety shutdown of 
motor starters, U 1 is not switched off.