ET 200S Distributed I/O System - Fail-Safe Modules 
Installation and Operating Manual, 08/2008, A5E00103686-07 
61 
Fail-Safe Modules 
7
7.1  Introduction 
This chapter    
Fail-safe power modules and fail-safe digital modules are available for connecting digital 
sensors/encoders and actuators/loads to the ET 200S. This chapter provides the following 
information for each fail-safe module: 
●  Properties and special features 
●  Front view, terminal assignment for terminal modules and the block diagram 
●  Wiring diagram and programmable parameters 
●  Diagnostic functions, including corrective measures 
●  Technical specifications 
 
WARNING 
 
 
The safety characteristics in the technical specifications apply for proof test intervals of 
20 years and repair times of 100 hours. If a repair within 100 hours is not possible, then 
remove the respective module from the terminal module or switch off its supply voltage 
before 100 hours expires. 
Then proceed as described in the chapter "
Reactions to Faults (Page 41)". 
 
Description of Usable Standard Power Models and Terminal Modules 
Usable standard power modules and terminal modules are described in the ET 200S 
distributed I/O system operating instructions.