Fail-Safe Modules   
7.2 PM-E F pm DC24V PROFIsafe Power Module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
66  Installation and Operating Manual, 08/2008, A5E00103686-07 
Capacitive Crosstalk of Digital Input/Output Signals     
Readback errors may occur on the PM-E F pm DC24V PROFIsafe power module or on the 
F-DO modules if the fail-safe digital output and fail-safe digital input signals are routed 
through one cable. The module signals a short circuit in this situation. 
Cause 
The steep switching edge of the output driver during the sensor supply test of the 4/8 F-
DI DC24V PROFIsafe module may lead to crosstalk on other inactive output channels due to 
the coupling capacitance of the wire, for example, on the PM-E F pm DC24V PROFIsafe 
power module. This situation may lead to a response in the readback circuit in these 
channels. The module detects a cross circuit and performs safety-related shutdown. 
Remedy 
●  Use separate cables for the F-DI modules and F-DO modules or standard DO modules 
that are controlled by a PM-E F pm DC24V PROFIsafe. 
●  Coupling relay or diodes in the outputs 
●  Disable the sensor supply test if safety class requirements allow this. 
See also 
Assigning Modules of an ET 200S (Page 22) 
Properties of the 4 F-DO DC24V/2A PROFIsafe digital electronic module (Page 163)