EasyManua.ls Logo

Siemens POLYCOOL RWR470.10 - Changing Setpoints (for end users)

Siemens POLYCOOL RWR470.10
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Changing Setpoints (for end users)
Display Procedures
In stop mode, press <Enter> for 2 seconds and release it to activate the Menu mode.
.
+
-
When the icon is blinking, press <Plus> or
<Minus> to navigate to the menu, and
then press <Enter> to proceed.
Contents under the Parameter Menu may vary with the privilege right of the user.
For end users, select “NO,” and press <Enter > to proceed.
For service men and factory users, select “EU” or”ID”,and press <Enter> to input the
4-digit password .
.
+
-
For end users, parameters in the “ST” group
will by default be displayed.
Press <Plus> and <Minus> to navigate to the
parameter and press<Enter> to continue.
Or, continuously press <Esc> to exit out of the current level and back to the desired
menu level.
The following list is parameters contained in the “ST” group.
Para-
meter
Descriptions De-
fault
Min. Max. Unit Res Privi-
lege
ST01
Setpoint of compressors in cooling mode (End User) 12 ST11 ST12 ºC/ 0.1 0
ST02
Setpoint of compressors in heating mode (End User) 40 ST13 ST14 ºC/ 0.1 0
ST03
Adjustable temperature band of compressor in Cooling mode 1 0 10 ºC 0.1 0
ST04
Adjustable temperature band of compressor in Heating mode 1 0 10
ºC
0.1 0
ST05
Setting temperature for heating temperature compensate function 20 0 30 ºC 0.1 0
ST06
Compensate factor for heating temperature compensate function 6 0 30
-
0.1 0
ST07 Temperature Scope of outside when the boiler started 0 -10 20 ºC 0.1 0
ST08 Setpoint of outside temperature when the boiler started 5 1 20
ºC
0.1 0
ST09 Setpoint of hotwater temperature in the life 50 ST15 ST16 ºC 0.1 0
ST10 Band of hotwater temperature in the life 3 1 10
ºC
0.1 0
ST11
Minimum setpoint in cooling
10 0 ST12 ºC 0.1 0
ST12
Maximum setpoint in cooling
40 ST11 60
ºC
0.1 0
ST17 Band of adjusting time 30 1 1000
Sec
1 0
11/28
Siemens Building Technologies SIEMENS Controller HEAT PUMP controller
HVAC Products 27.11.2006