Siemens POLYCOOL RWR470.10 - 10 Paramter Tables; Compressor Settings; Condenser Settings; Evaporator Settings

Siemens POLYCOOL RWR470.10
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Paramter Tables
Compressor Settings
<Second: Sec; Minute: Min; Hour: Hr>
Para-
meter
Descriptions De-
fault
Min
.
Max. Unit Res. Privi
-
lege
CM01 Compressor minimum ON time 180 1 1000 Sec 1 1
CM02 Compressor minimum OFF time 180 1 1000 Sec 1 1
CM03 Start Delay between two compressors 10 0 100 Sec 1 1
CM04 Shut down delay between two compressors 30 0 1000 Sec 1 1
CM05 Compressor ON delay (outdoor pump ON) 10 0 150 Sec 1 1
CM06 The number of compressors 2 1 2 - 1 2
CM07 The direction indicator of four-way valves( 1 or 0 indicates
heating mode)
1 0 1 1
CM08 Compressor consecutive running time for discard 30000 0 5000
0
Hr 10 1
Condenser Settings
Para-
meter
Descriptions De-
fault
Min Max Unit Res. Privi-
lege
CN01
- outdoor pump ON delay (indoor pump ON)
10 0 150 Sec 1 1
CN02 outdoor pump ON delay (compressor OFF) 10 0 150 Sec 1 1
Evaporator Settings
Para-
meter
Descriptions De-
fault
Min. Max. Unit Res. Privi
-lege
EV01 Control Mode
- 0=pump with circulate continuously
- 1= The water pump with the compressor ON/ OFF but
ON/ OFF
0 0 1 - 1 1
EV02 Indoor reference sensor:
- - 0=RT (return temperature sensor)
- 1=ST (supply temperature sensor)
0 0 1 - 1 1
EV03 indoor pump Off delay (compressor OFF) 60 CN02 1000 Sec 1 1
21/28
Siemens Building Technologies SIEMENS Controller HEAT PUMP controller
HVAC Products 27.11.2006