User Settings
Para-
meter
Descriptions De-
fault
Min. Max. Unit Res Privi-
lege
ST01
Setpoint of compressors in  cooling mode (End User) 12 ST11 ST12 ºC/ 0.1 0
ST02
Setpoint of compressors in heating mode (End User) 40 ST13 ST14 ºC/ 0.1 0
ST03
Adjustable temperature band of compressor in Cooling mode 1 0 10 ºC 0.1 0
ST04
Adjustable temperature band of  compressor in Heating mode 1 0 10
ºC
0.1 0
ST05
Setting temperature for heating  temperature compensate function 20 0 30 ºC 0.1 0
ST06
compensate factor for heating  temperature compensate function 6 0 30
-
0.1 0
ST07 Temperature Scope of outside  when the boiler started 0 -10 20 ºC 0.1 0
ST08 Setpoint of outside temperature when the boiler started 5 1 20
ºC
0.1 0
ST09 Setpoint of hotwater  temperature in the life  50 ST15 ST16 ºC 0.1 0
ST10 band  of hotwater  temperature in the life 3 1 10
ºC
0.1 0
ST11
minimum setpoint in cooling
10 0 ST12 ºC 0.1 0
ST12
maximum setpoint in cooling
40 ST11 60
ºC
0.1 0
ST13
minimum setpoint in heating
20 0 ST14 ºC 0.1 1
ST14
maximum setpoint in heating
55 ST13 80
ºC
0.1 1
ST15
minimum setpoint of  hotwater  temperature in the life
20 0 ST16
ºC
0.1 1
ST16
maximum setpointf  hotwater  temperature in the life
55 ST15 80
ºC
0.1 1
ST17 band of adjusting time
User Interface
Para-
meter
Descriptions De-fault Min. Max. Unit Res. Privi-
lege
UI01
Password for service user 1234 0 9999 - 1 1
UI02
Password for factory user 4321 0 9999 - 1 2
Alarm Settings
Para-
meter
Descriptions De-
fault
Min. Max. Unit Res. Privi-
lege
AL01 Protecting Setpoint for low outlet water temperature 
3 1 10 ºC 1 1
AL02 Band of low outlet  water temperature 
2 1 10 ºC 1 1
AL03
Protecting Setpoint for high outlet water temperature  55 1 100 ºC 1 1