37 / 46
Siemens Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS CM2N1602en_05
Building Technologies ETS engineering 2018-09-14
Visible parameter name in ETS Range
(Default)
5.5.3 Room relative humidity sensor
Humidity: Send following change by
Humidity: Send cyclically after 1; 2…45; 60 (15 min) min
5.5.4 Room relative humidity control
To display this section, enable the option “Activate room humidity control” in Device
Default switching point stage 1 (%r.h.)
Default switching point stage 2 (%r.h.)
Default switching point stage 3 (%r.h.)
Hysteresis 2;3;4;5;7;10 (5%) %r.h.
If room humidity exceeds a switching point r.h., the control value r.h.
for the respective stage is switched on.
Control value r.h. is switched off again when room humidity
< switching point r.h. – hysteresis.
Control value stage 0 (%)
Control value stage 1 (%) (>stage 0)
Control value stage 2 (%) (>stage 1)
Control value stage 3 (%) (>stage 2)
If room humidity exceeds switching point r.h., the control value
parameterized for this stage is issued.
The control value again issues the next lower stage value when room
humidity < switching point r.h. – hysteresis.
Send cyclically after
Do not send cyclically
1;2;3...30;45;60 (15 min)
min.
X X X X X X X