Functions
Operating modes
3
10
| 52
A6V11917618_en--_b
Comfort mode
In Comfort mode, the thermostat maintains the Comfort setpoint temperature.
The setpoint can be defined via parameter P64, locally adjusted via the
Up/Down buttons or remotely selected via BACnet. Factory setting is 22 °C.
The Comfort mode change can be delayed, typically used in combination with a
presence detector:
Delay from Comfort to Standby (Economy) mode is defined via parameter
P11.
Delay from Standby (Economy) to Comfort mode is defined via parameter
P12.
In Comfort mode, the fan can be set to automatic or manual fan speed:
Low, medium or high.
Standby (Economy)
In Standby (Economy) mode, a preset setpoint can be defined via parameters
P06 and P07. Factory setting is 15 °C for heating and 30 °C for cooling.
The thermostat switches to Standby (Economy) mode
If Standby (Economy) is sent via BACnet
If the thermostat gets an operating mode switchover contact (e.g. keycard
contact or presence detector).
OFF mode
The thermostat and the fan are switched off, and the thermostat gets no
heating or cooling output. Mold protection function can overrun the fan speed.
NOTICE
No protecting heating or cooling control in OFF mode
Risk of frost or risk of over temperature
For more information about the thermostat functions refer to chapter
'Additional functions [ 12]'.