Communication
Control parameters
8
32
| 52
A6V11917618_en--_b
Object
name
Object ID
Description
Values
Writeable
ROpMod
Multistate
value, 5
Room operating
mode
1 = Off
2 =
Economy/Standb
y
3 = Not used
4 = Not used
5 = Comfort
6 = No remote
control
Yes
BtnCnf
Multistate
value, 6
Buttons active
1 = No active
buttons
2 = Only On/Off
button active
3 = Only
Up/Down
buttons active
4 = On/Off and
Up/Down
buttons active
5 = Only fan
button active
6 = On/Off and
fan button active
7 = Up/Down
and fan button
active
8 = All buttons
active
Yes
Valve 1
setting
Multistate
value, 7
Set valve 1 type
1 = DC valve
2 = PWM
3 = On/Off
4 = 3-position
valve
Yes
Valve 2
setting
Multistate
value, 8
Set valve 2 type
1 = DC valve
2 = PWM
3 = On/Off
4 = 3-position
valve
Yes
8.3 Control parameters
A number of control parameters can be readjusted to optimize control
performance. This can be done on the thermostat via HMI or via commissioning
/ operating tool. These parameters can also be set during operation without
opening the unit.
All control parameter settings are retained in the event of a power failure.