8.2 Communication objects
Analog inputs
Object
name
Object ID
Description
Unit
Writeable
TR
Analog input, 0
Room temperature
°C
No
TChover
Analog input, 1
Change over
temperature
°C
No
AI1
Analog input, 2
Analog input
°C
No
UI1
Analog input, 3
-
V
No
Tsu
Analog input, 4
Supply air temperature
°C
No
Analog values
Object
name
Object ID
Description
Unit
Writeable
AO1
Analog value, 0
Analog output
V
No
AO2
Analog value, 1
Analog output
V
No
SpTRShft
Analog value, 2
Setpoint shift value
°C
No
SpTR
Analog value, 3
Controller setpoint
°C
No
LoopOut
Analog value, 4
Control output
%
No
HclVlvPos
Analog value, 5
Heating coil valve
position
%
No
CclVlvPos
Analog value, 6
Cooling coil valve
position
%
No
Not used
Analog value, 7, 8
-
-
No
SpHEco
Analog value, 9
Heating setpoint for
Standby (Economy)
°C
Yes
SpCEco
Analog value, 10
Cooling setpoint for
Standby (Economy)
°C
Yes
Not used
Analog value, 11
-
-
-
PrSpShft
Analog value, 12
Setpoint displacement
during presence
°C
Yes
HclVlvPos
Man
Analog value, 13
Manual value heating
output
%
Yes
CclVlvPos
Man
Analog value, 14
Manual value cooling
output
%
Yes
TRRemote
Analog value, 15
Remote control of
room temperature
°C
Yes
StbyDBand
Analog value, 16
Dead band for Standby
mode
°C
Yes
Not used
Analog value, 17-
26
-
-
-
FanVarSpd
Min
Analog value, 27
Lowest possible speed
for the DC fan
%
Yes