Commissioning
13
44
| 52
A6V11917618_en--_b
13 Commissioning
Applications
The BACnet MS/TP room thermostats are delivered with a fixed set of
applications and related parameters. The relevant application is selected and
activated during commissioning using the local HMI or commissioning tools for
BACnet MS/TP.
The factory settings can be changed by using the display and buttons on the
controller. The Up/Down buttons change the parameter values; the changes
are confirmed with the On/Off button.
Wizard setting
The first time the thermostat is powered on, a setup wizard is available to help
with the first settings.
This wizard is a list of parameters that help define the major functions of the
product in order to facilitate commissioning.
Parameter
Name
Range
Factory setting
P01
Application
2 = 2-pipe system
3 = 4-pipe system
4 = 2-pipe system with
electric heater
3 = 4-pipe system
P77
Fan output type
0 = 1-, 2- or 3-speed fan
1 = DC fan
0 = 1-, 2- or 3-speed
fan
P78
Valve 1 output
type
0 = DC valve
1 = PWM (Thermal valve)
2 = On/Off (Thermostat
function)
3 = 3-position valve
0 = DC valve
P79
Valve 2 type *)
0 = DC valve
1 = PWM (Thermal valve)
2 = On/Off (Thermostat
function)
3 = 3-position valve
0 = DC valve
P58
BACnet MS/TP
MAC address
Must be unique within an
MS/TP network
0-99, as per device
label
P59
BACnet MS/TP,
device id, the
4 lowest digits.
-
Lowest 4 digits of
device ID, as per
device label
P60
BACnet MS/TP,
device id, the
3 highest digits
-
Highest 3 digits of
device ID, as per
device label
P62
Baud rate
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
3 = 76800 bps
3 = 76800 bps
*) Locked to On/Off when thermostat is set to 2-pipe with electric heater
application.